Free Tool

Gas Rate Calculator

Free tool from FC Training Academy. Work out heat input from a meter test and check it against the data plate.

Gas Rate Test Timer

Test duration

Take the start reading, press Start, and take the end reading when the alarm sounds.

2:00

Calculate Gas Heat Input

Enter the appliance's rated net heat input to check tolerance

Using CV: 38.76 MJ/m³ | Ratio: 1.11

Net heat input (rated 18 kW)

17.46 kW

Volume (m³)

0.0600

Flow (m³/h)

1.80

Gross kW

19.38

Data plate comparison

Within tolerance (-3.0%)

Natural gas CV 38.76 MJ/m³ / 1040 Btu/ft³, ratio 1.11. LPG CV 93.2 MJ/m³ / 2500 Btu/ft³, ratio 1.09. For guidance only — always refer to current Gas Safe technical standards.

Combustion Ratio Check (CO/CO₂)

Enter the flue gas analyser readings and the ratio limit from the manufacturer's instructions (MI).

CO/CO₂ ratio

0.0009

Below limit — acceptable

Ratio = CO ÷ (CO₂ × 10,000). Always refer to the appliance manufacturer's instructions for the applicable limit.

Recent Gas Rate Calculations

No saved calculations yet. Run a calculation above and press "Save this result".

Tolerance shown is the common +5% / -10% of the rated net input. Always follow the manufacturer's instructions for the appliance.